Promark
WhatsApp
Vutlan VT591 Leak Sensor + WLC Leak Detection Cable

Vutlan VT591 — Water Leak Sensor (with WLC Detection Cable)

Analog leak sensor that detects water or conductive liquid anywhere along the WLC detection cable. Provides perimeter protection under raised floors, around cooling units and at cabinet bases; alarms are sent as SNMP trap, e-mail or SMS. The WLC cable is ordered separately in 3–25 m lengths.

Water LeakLeak DetectionWLCAnalogRaised Floor
Vutlan VT591 — Water Leak Sensor (with WLC Detection Cable)

From the same family

Specifications

Type
Analog water leak sensor + WLC sensing cable
Manufacturer
Vutlan s.r.o. (Bratislava, Slovakia)
Detects
Water (clean/dirty/pure), acid, alkali, alcohol, conductive liquids
Cable options
WLC3, WLC6, WLC10, WLC15, WLC25 (ordered separately)
Cable diameter
Ø 6.5 mm
Max distance
100 m (from master unit / VT408); WLC max 100 m
Response time
15 s
Connection
RJ11/RJ12 6P4C output, 2-wire WLC input; no daisy chain
Power consumption
60 mW
Dimensions
60 × 18 × 18 mm, 60 g
Operating conditions
−10…+80 °C, 5–95% RH (non-condensing)
Compatible
VT225t, VT335G, VT336t, VT825G, VT855G, VT604G, VT608G and VT408 analog ports
GTIN
8588009886211
Warranty
90 days (Vutlan extension/accessory warranty); made in the EU

Key features

  • Detection: resistance drop in the WLC cable — clean, polluted and distilled water, acids, alkalis, alcohols and other conductive liquids.
  • WLC cable options: WLC3, WLC6, WLC10, WLC15, WLC25 (3–25 m); Ø6.5 mm; ordered separately.
  • Max distance: 100 m from the master unit or VT408; max WLC cable length 100 m.
  • Response time 15 s; recovery depends on how fast the cable dries.
  • Analog sensor — RJ11/RJ12 6P4C output, 2-wire WLC input; not chainable.
  • Operating: −10…+80 °C, 5–95% RH non-condensing; 60 mW.
  • 60 × 18 × 18 mm, 60 g; screw and adhesive mounting.
  • Compatible: VT225t, VT335G, VT336t, VT825G, VT855G, VT604G, VT608G and VT408 analog ports.
  • Promark: leak-risk analysis, cable routing plan and installation.

Typical applications

01

Perimeter leak protection under data-center raised floors.

02

Around cooling units (CRAC/CRAH) and chilled-water lines.

03

Rack / cabinet bases and cable trays.

04

UPS and battery rooms, switchboard rooms.

05

Water-sensitive areas such as archives, museums and warehouses.

Related Solutions

Related Products

Vutlan VT591 — Water Leak Sensor (with WLC Detection Cable)

Analog leak sensor that detects water or conductive liquid anywhere along the WLC detection cable. Provides perimeter protection under raised floors, around cooling units and at cabinet bases; alarms are sent as SNMP trap, e-mail or SMS. The WLC cable is ordered separately in 3–25 m lengths.