Promark
WhatsApp
Power & DC

Eltek DC Power System — Flatpack S & Flatpack2 (-48 V)

-48 V DC power systems for telecom and data centers. Flatpack S 1U: controller, rectifiers, battery and load distribution in a single 1U chassis, 262 mm deep, 40 A (2R) or 100 A (3R) output. Flatpack2: 2000 W and 3000 W HE/SHE rectifiers, from the 2U 150 A Integrated rack up to 5U–8U 700 A systems. Controller per system: Smartpack S, Smartpack R or Smartpack2, with remote monitoring over Ethernet. For base stations, PBX rooms, fiber and transmission nodes.

Platform guide: what it does, model comparison, FAQ
Eltek

Scope / deliverables

  • Eltek Flatpack S 1U — compact complete system: Smartpack S controller + Flatpack S rectifiers (48/1000 HE or 48/1800 HE) + battery and load distribution in a single 19" 1U chassis; 262 mm system depth
  • Flatpack S 2R: 1 controller + 2 rectifiers, max 40 A; 230 VAC 1-phase or 2×1-phase input; front load 4×30 A MCB or 7×15 A fuse, optional 7×30 A MCB drawer (LVLD); battery 2×40 A
  • Flatpack S 3R: 1 controller + 3 rectifiers, max 100 A; 230 VAC 3×1-phase / 3-phase (Δ) or 230/400 VAC 3-phase (Y); rear load 2×80 A; battery 2×80 A (M6 cable lug)
  • Eltek Flatpack2 2U Integrated: 19" 2U, max 150 A at -48 VDC; Smartpack R controller; 2 battery breakers (max 100 A), 6 load MCBs (2–32 A or 2–60 A); optional LVBD and PLD; system operating temperature -40…+65 °C
  • Flatpack2 5U–8U Integrated: -48 VDC 600 A (48/2000 or 48/3000 HE/SHE) and 700 A (36 kW, 48/3000) models, Smartpack R; Flatpack2 5U–7U Integrated: 300 A / 500 A, Smartpack2 or Smartpack S
  • Flatpack2 48 V rectifier: 2000 W (41.7 A) and 3000 W (62.5 A); HE 96% at nominal input, SHE up to 97.8% peak efficiency; 53.5 VDC default output; 48/2000 HE: 85–300 VAC input, 43.5–57.6 VDC adjustable, -40…+75 °C (derating above 55 °C), 109 × 41.5 × 327 mm, 1.95 kg; hot-plug
  • Control and monitoring: Smartpack S (Flatpack S, 5U–7U), Smartpack R (2U and 5U–8U Integrated), Smartpack2 (5U–7U and industrial systems); CAN bus to the rectifiers, remote monitoring over Ethernet, digital inputs and alarm relays
  • N+1 redundancy: the rectifier count is calculated from load current plus battery charge current and one extra module is fitted; total current cannot exceed the system limit (e.g. 150 A for the 2U Integrated)
  • Applications: mobile/wireless telecom (LTE/4G, WiMAX, DAS, microwave), fixed telecom (central office, FTTx, fiber, broadband), data center DC power
  • Design standards: EN IEC 62368-1 (electrical safety); ETSI EN 300 386, EN 61000-6-x (EMC); ETSI EN 300 019-2-1/2/3 (environmental)
  • Promark: DC power system sizing, installation, commissioning, SNMP/NMS integration, battery integration, spare module supply and periodic maintenance