Eltek Flatpack2 — Telecom DC Rectifier Family (24/48/60 V, HE & SHE)
High-efficiency (96% at nominal input) Flatpack2 HE 48V rectifier system for telecom and data center DC power infrastructure. 2000W and 3000W module options scaling from 8kW 2U racks with complete distribution to multi-cabinet, multi-MW installations. MTBF >350,000 h (2000W) / >300,000 h (3000W) at 25 °C. The family also includes 24/1800 HE, 48/2000 and 48/3000 SHE (up to 97.8% efficiency), 48-60/2000 HE and 60/3000 SHE modules; the 110 and 220 V models are on the Industrial DC page.

From the same family
Specifications
- Type
- DC power rectifier system (48V telecom)
- Manufacturer
- Eltek
- Module power
- 2000W and 3000W (HE)
- Efficiency
- 96% @ nominal input (patented HE)
- Output
- -48V DC
- Min system
- 8kW 2U rack
- Max system
- Multi-cabinet, multi-MW
- Power density
- 33 W/inch³ (max)
- Certification
- CE, UL; EN/IEC/UL 62368-1; ETSI EN 300 386; Telcordia NEBS GR1089
- MTBF (Telcordia SR-332, 25 °C)
- >350 000 h (2000W) / >300 000 h (3000W)
- Hot-plug
- Rectifier modules
- Management
- Smartpack-family controller, CAN bus
- Operating temperature
- -40 … +75 °C (derating >55 °C)
- Other variants
- 24/1800 HE · 48/2000 SHE · 48/3000 SHE · 48-60/2000 HE · 60/3000 SHE
- SHE efficiency
- up to 97.8%
Key features
- Patented HE (High Efficiency) technology — 96% efficiency at nominal input.
- Modular 2000W and 3000W rectifier options — scale with additional modules.
- High power density — up to 33 W/inch³.
- Broad application set: telecom mobile/fixed, datacenter, broadcast, SCADA, broadband.
- System scale: from 8kW 2U racks with complete distribution to multi-cabinet, multi-MW installations.
- Wide operating temperature: -40 … +75 °C (power derating above 55 °C).
- MTBF (Telcordia SR-332, 25 °C): >350,000 h (2000W) / >300,000 h (3000W).
- Electrical safety EN/IEC/UL 62368-1; EMC: ETSI EN 300 386, Telcordia NEBS GR1089.
- Global compliance (CE, UL).
- Monitoring and control by a Smartpack-family controller over CAN bus.
- Battery distribution + load distribution as integrated system components.
- Hot-plug rectifier — add/replace without interruption.
- Family variants: 24/1800 HE (75 A, 21.75–28.8 VDC, up to 95%); 48/2000 SHE and 48/3000 SHE (41.7 / 62.5 A, up to 97.8%, input 85–264 VAC); 48-60/2000 HE (41.6 A, 39.9–72 VDC, 96.2%); 60/3000 SHE (50 A at 60 VDC, 54–72 VDC, up to 97.8%).
- System options: complete 2U, 5U–7U and 5U–8U Integrated racks are on the Flatpack2 Integrated page; the 2U Integrated rack uses the Smartpack R controller.
Typical applications
Telecom base station (BTS / LTE / 4G / WIMAX) DC power.
Data-center 48V power layer + UPS backup.
Central Office — telephone switch and server DC supply.
Fiber / broadband / microwave carrier infrastructure.
SCADA + power distribution — critical infrastructure.
Related Solutions
Related Products

Eltek Flatpack2 Integrated — Complete 48 V DC Power Systems (150–700 A)
Complete -48 VDC power systems configured with Flatpack2 rectifiers, controller, battery and load distribution. 2U Integrated up to 150 A, 5U–7U Integrated 300 A / 500 A, 5U–8U Integrated 600 A and 700 A (36 kW). Smartpack R, Smartpack2 or Smartpack S controller; hot-plug HE/SHE rectifiers, LVBD, plug-in battery breakers and DIN-rail load MCBs. For PBX rooms, base stations, transmission and the data center DC power layer.
Details
Eltek Flatpack2 Industrial — 110/220 VDC Rectifier and Battery Charger Systems
110–220 VDC battery charging and DC supply systems for substations, switchgear, control and protection, SCADA and emergency lighting. Flatpack2 110 V and 220 V HE rectifiers work with lead-acid and NiCd batteries. The 19" 2U Integrated system delivers 8 kW at 110–220 V and 12 kW at 24–125 V with 4 modules; IBB IP cabinet systems offer up to IP55 and up to 300 A DC output. Smartpack2 controller: web interface, SNMP and Modbus.
Details
Eltek Flatpack S — 1U Compact 48V DC Power System
Compact 48V DC power system in 262 mm depth, 1U high — fits in small infrastructure cabinets, used in small switches and branches. Smartpack S controller + 2-3 rectifiers (1000W or 1800W modules) + battery + load distribution in one 1U platform. Remote management over Ethernet.
Details
Exide GNB Sprinter P12V875 — 12V 41Ah VRLA AGM Battery
High-rate emergency backup battery for UPS and security systems — Exide GNB Sprinter P/XP series (NAPW120875HP0MC). 1157W per block at 10-minute 1.6V/C discharge @ 25°C, 41Ah at 10-hour 1.8V/C. EUROBAT 'Long Life' 10-12 year design life, maintenance-free AGM technology.
DetailsOpenScape 4000 EcoServer 2 — Mission-Critical Communications Platform
Enterprise-grade PBX server for government, hospital, airport and large-campus deployments — Linux-based (SLES), 12,000 subscribers per single system, up to 100,000 when networked, with geo-redundant Hot-Standby Duplex.
DetailsHigh-efficiency (96% at nominal input) Flatpack2 HE 48V rectifier system for telecom and data center DC power infrastructure. 2000W and 3000W module options scaling from 8kW 2U racks with complete distribution to multi-cabinet, multi-MW installations. MTBF >350,000 h (2000W) / >300,000 h (3000W) at 25 °C. The family also includes 24/1800 HE, 48/2000 and 48/3000 SHE (up to 97.8% efficiency), 48-60/2000 HE and 60/3000 SHE modules; the 110 and 220 V models are on the Industrial DC page.