Eltek Flatpack2 Industrial — 110/220 VDC Rectifier and Battery Charger Systems
110–220 VDC battery charging and DC supply systems for substations, switchgear, control and protection, SCADA and emergency lighting. Flatpack2 110 V and 220 V HE rectifiers work with lead-acid and NiCd batteries. The 19" 2U Integrated system delivers 8 kW at 110–220 V and 12 kW at 24–125 V with 4 modules; IBB IP cabinet systems offer up to IP55 and up to 300 A DC output. Smartpack2 controller: web interface, SNMP and Modbus.

Specifications
- Type
- Industrial DC power and battery charger system
- Manufacturer
- Eltek (Delta Group)
- Nominal output
- 110–125 VDC and 220 VDC (2U Integrated 24–125 V model: 24 / 48 / 60 / 110 / 125 V)
- Rectifiers
- Flatpack2 110-125/2000 HE (241115.805) · 110-120/20A HE (241119.805) · 220/2000 HE (241115.815) · 220/10A HE (241119.815)
- Module power / current
- 2000 W / 16.7 A · 3025 W / 20 A · 2000 W / 9.16 A · 2800 W / 10 A
- Output adjustment range
- 89.2–171.6 VDC (110/2000) · 90–151.25 VDC (110/20A) · 178.5–297 VDC (220/2000) · 198–280 VDC (220/10A)
- Efficiency
- Above 94% (110 V) · above 95% / 95.5% (220 V)
- Battery type
- Lead-acid or NiCd; 50–120 Pb / 82–180 NiCd cells on the 2U 110–220 V system
- Input
- 85–300 VAC (the 2000 W models also accept 85–300 VDC) · 85–305 VAC (20A / 10A models); power factor 0.99
- 2U Integrated system
- 4 modules; 8 kW (110–220 V) / 12 kW (24–125 V); 482 × 470 × 89 mm (110–220 V); IP20; -40…+55 °C
- IBB IP cabinet system
- Up to IP55; 24–220 VDC up to 300 A / 16 kW; 230 VAC up to 6.75 kVA
- Controller
- Smartpack2 (Touch, Industrial basic); display and keys, web interface, SNMP, Modbus
- Module operating temperature
- -40…+75 °C (derating above 50 / 55 °C)
- MTBF (Telcordia SR-332, 25 °C)
- >391 000 h (2000 W) / >400 000 h (20A, 10A)
Key features
- Flatpack2 110-125/2000 HE: 2000 W, 16.7 A; 122.5 VDC default, 89.2–171.6 VDC adjustable; 54–71 lead-acid or 85–104 NiCd cells; efficiency above 94%
- Flatpack2 110-120/20A HE: 3025 W, 20 A; 90–151.25 VDC; 54–60 lead-acid or 86–91 NiCd cells; efficiency above 94%
- Flatpack2 220/2000 HE: 2000 W, 9.16 A at 220 VDC; 245.3 VDC default, 178.5–297 VDC adjustable; 108–122 lead-acid or 170–180 NiCd cells; efficiency above 95%. 220/10A HE: 2800 W, 10 A; efficiency above 95.5%
- Common module data: AC input 85–300 VAC (the 2000 W models also accept DC input), power factor 0.99; operating temperature -40…+75 °C; 109 × 41.5 × 327 mm, 1.95 kg; hot-plug, OR-ing diode output
- Flatpack2 Integrated 19" 2U: 4 rectifier slots; 24–125 V model 12 kW, 110–220 V model 8 kW; rear bulk DC output on M6 bolts; Smartpack2 Touch controller; 3 alarm relays on 110–220 V, optional Fleximonitor and relay board; earth fault alarm; -40…+55 °C
- IBB IP: cabinet system built from pre-tested building blocks, protection class up to IP55; IBF AC/DC and DC/DC blocks 24–220 VDC up to 300 A / 16 kW; IBF DC/AC 230 VAC up to 6.75 kVA; integrated DC/AC distribution and battery fuse; 3.2" display, Ethernet, web, SNMP, Modbus TCP
- Smartpack2 controller: local operation via display and keys, remote operation via web interface, SNMP and Modbus; low/high output voltage, earth fault, temperature, mains outage, battery remaining capacity and breaker-tripped alarms
Typical applications
Substations and switchgear: 110/220 VDC supply for protection relays and breaker tripping circuits
Power generation and distribution plants: control, protection and SCADA communication equipment
Emergency lighting and alarm systems
Railway and metro: signaling, control and safety systems
Oil, gas and process plants, offshore platforms (IBB IP, up to IP55)
Replacement of older 110/220 V rectifier systems (e.g. the Eltek PSS series)
Related Solutions
Related Products

Eltek Flatpack2 — Telecom DC Rectifier Family (24/48/60 V, HE & SHE)
High-efficiency (96% at nominal input) Flatpack2 HE 48V rectifier system for telecom and data center DC power infrastructure. 2000W and 3000W module options scaling from 8kW 2U racks with complete distribution to multi-cabinet, multi-MW installations. MTBF >350,000 h (2000W) / >300,000 h (3000W) at 25 °C. The family also includes 24/1800 HE, 48/2000 and 48/3000 SHE (up to 97.8% efficiency), 48-60/2000 HE and 60/3000 SHE modules; the 110 and 220 V models are on the Industrial DC page.
Details
Eltek Flatpack2 Integrated — Complete 48 V DC Power Systems (150–700 A)
Complete -48 VDC power systems configured with Flatpack2 rectifiers, controller, battery and load distribution. 2U Integrated up to 150 A, 5U–7U Integrated 300 A / 500 A, 5U–8U Integrated 600 A and 700 A (36 kW). Smartpack R, Smartpack2 or Smartpack S controller; hot-plug HE/SHE rectifiers, LVBD, plug-in battery breakers and DIN-rail load MCBs. For PBX rooms, base stations, transmission and the data center DC power layer.
Details
Exide GNB Sprinter P12V875 — 12V 41Ah VRLA AGM Battery
High-rate emergency backup battery for UPS and security systems — Exide GNB Sprinter P/XP series (NAPW120875HP0MC). 1157W per block at 10-minute 1.6V/C discharge @ 25°C, 41Ah at 10-hour 1.8V/C. EUROBAT 'Long Life' 10-12 year design life, maintenance-free AGM technology.
Details
Vutlan VT520 — AC Voltage Monitor
Sensor that monitors AC mains — connects to Vutlan monitoring units for presence/absence detection, voltage level and outage alerts. Instant SMS/email/SNMP alarm on power cut.
Details110–220 VDC battery charging and DC supply systems for substations, switchgear, control and protection, SCADA and emergency lighting. Flatpack2 110 V and 220 V HE rectifiers work with lead-acid and NiCd batteries. The 19" 2U Integrated system delivers 8 kW at 110–220 V and 12 kW at 24–125 V with 4 modules; IBB IP cabinet systems offer up to IP55 and up to 300 A DC output. Smartpack2 controller: web interface, SNMP and Modbus.