Exide VRLA AGM Battery (12V 41Ah / 56Ah)

Exide GNB Sprinter maintenance-free AGM VRLA batteries — P12V875 (12V 41Ah, 1157W/block at 10-minute discharge) and XP12V1800 (12V 56.4Ah, 1840W/block at 10-minute discharge). EUROBAT 'Long Life' 10–12 year design life, standard or UL 94-V0 flame-retardant version, IEC 60896-21/-22. For UPS, telecom DC power and security systems; configured as a 4×12V = 48V battery bank for Eltek Flatpack2 and Flatpack S systems.

Platform guide: what it does, model comparison, FAQ

Scope / deliverables

  • P12V875 technical specs: 12V nominal, 41Ah (C10 @1.80V/C, 25°C), 10-minute power: 1157W/block @ 1.60V/C; short circuit: 1178A; internal resistance: 10.6mΩ (IEC 60896-21/22)
  • XP12V1800 technical specs: 12V nominal, 56.4Ah (C10, 1.80V/cell); 10-minute power: 1840W/block @ 1.60V/cell, 25°C; short circuit: 1558A; 220×172×219mm (235mm incl. terminals); 21.0 kg
  • P12V875 selected discharge data: 10 min @ 1.80V/C: 1013W — 1h @ 1.80V/C: 301W — 2h @ 1.80V/C: 183W; Constant current C10: 4.1A
  • Design life: 10–12 years — EUROBAT 2015 Long Life class; flame retardant version available (UL 94-V0 container); standard: UL 94-HB polypropylene
  • Technology: AGM high-compression glass mat VRLA; 99% internal gas recombination (very low gassing); lead-calcium alloy grid plates (superior corrosion resistance); fully maintenance-free
  • P12V875 dimensions and weight: 200×169×176mm (L×W×H); 14.5 kg; terminal: M6 screw, 6Nm torque; operating range: -40°C~+55°C; float charge: 2.27V/cell @ 25°C
  • P12V875 approvals and transport: UL; IATA DGR Clause A67 — unrestricted rail, road, sea and air; IEC 60896-21/-22; ISO 9001 European manufacture (Castanheira, Portugal)
  • Battery bank for Eltek Flatpack2 8kW: 4×P12V875 series = 48V, 41Ah — two parallel strings = 82Ah; Promark sizes per load current and autonomy requirement
  • Temperature warning: capacity drops >25°C ambient; design life shortens above 30°C — climate control recommended for battery room
  • Promark: battery bank sizing (load + autonomy analysis), installation, periodic capacity testing, end-of-life replacement and recycling coordination

Tags

ExideSprinterP12V875XP12V180012V41Ah56AhAGMVRLAUPSDCTelecomEUROBATULMaintenance-Free10 YearsIEC 60896