# Exide GNB Sprinter XP12V1800 — VRLA/AGM Battery (12V 56.4Ah)

URL: https://www.promark.tr/en/products/exide-12v-56ah
Category: Power & DC
Family: [Exide VRLA AGM Battery (12V 41Ah / 56Ah)](https://www.promark.tr/en/products/battery-banks)

High-wattage maintenance-free VRLA/AGM battery — for UPS, telecom DC power and emergency lighting. 1840 W/block over a 10-minute discharge (1.60 V/cell, 25 °C); EUROBAT 2015 'Long Life 10–12 years' classification; standard or UL 94-V0 flame-retardant version; designed in accordance with IEC 60896-21/-22.

## Key features

- High-compression absorbent glass-mat (AGM) separator — VRLA, maintenance-free.
- No water/acid top-up needed throughout service life.
- Nominal: 12V / 56.4Ah (C10, 1.80 V/cell); 1840 W/block over a 10-minute discharge (1.60 V/cell, 25 °C).
- Short-circuit current: 1558A.
- EUROBAT 2015 'Long Life — 10–12 years' classification.
- Polypropylene (PP) case; standard (UL 94-HB) or UL 94-V0 flame-retardant version.
- Designed in accordance with IEC 60896-21/-22.
- Dimensions: 220 × 172 × 219 mm (L × W × H; 235 mm height including terminals); weight 21.0 kg.
- Applications: UPS backup, emergency lighting, security systems, telecom DC power.
- Promark: capacity sizing per load duration, series/parallel string planning, cabinet integration, periodic maintenance schedule.

## Specifications

- **Type:** VRLA/AGM maintenance-free battery
- **Manufacturer:** Exide Technologies — GNB Industrial Power
- **Series:** GNB Sprinter XP
- **Model:** XP12V1800
- **Voltage:** 12V
- **Capacity:** 56.4Ah (C10)
- **10-min watt:** 1840 W/block (1.60 V/cell, 25 °C)
- **Short-circuit current:** 1558 A
- **Dimensions:** 220 × 172 × 219 mm (L × W × H); 235 mm incl. terminals
- **Weight:** 21.0 kg
- **Certifications:** EUROBAT 2015 Long Life 10-12; IEC 60896-21/-22 (design); UL 94-V0 version optional
- **Case material:** Polypropylene (PP); UL 94-HB standard, UL 94-V0 optional
- **Design life:** 10-12 years (EUROBAT 'Long Life')
- **Application:** UPS, emergency lighting, security, telecom DC

## Use cases

- Hospital / critical facility UPS — mid-to-high capacity backup string.
- Telecom CO room DC power bank — paired with Eltek/Vertiv rectifiers.
- Government building emergency lighting.
- Industrial control room — uninterrupted PLC/HMI/SCADA supply.
- Data-center PDU backup — for mid-capacity UPS modules.

## For a quote and BOM

https://www.promark.tr/en/contact · +90 312 544 0915 · destek@promark.tr